TIA TSB-4979 2013 Edition, August 1, 2013 Practical Considerations for Implementation of Encircled Flux Launch Conditions in the Field
In stock
Warning: Last items in stock!
Availability date: 09/09/2021
Description / Abstract:
This Telecommunications Systems Bulletin (TSB) describes two
methods for implementing light sources to fulfill compliance
requirements for the EF launch condition. The EF guidelines can be
used for field testing optical attenuation of installed multimode
cabling for 850 nm and 1300 nm containing 50 μm and, when required,
62.5 μm graded-index fibers.
Since the most common high-speed applications currently run at
850 nm on 50 μm cabling, for dual wavelength sources it's best to
align the launch condition to the 850 nm EF target, then allow the
1300 nm launch to fall where it may. In almost all cases, the 1300
nm response will remain within its EF template also. This approach
reduces 850 nm launch uncertainty, possibly at the expense of the
1300 nm launch. Despite this trade-off, this is an improvement over
other launch conditions.
Since the EF template is different for 50 μm and 62.5 μm
cabling, two diffferent launch controllers are needed. One specific
launch controller adjusted for 50 μm EF response and another one
adjusted for 62.5 μm EF response are needed. This applies to all
types of controllers used with single or dual wavelength
sources.
The purpose of this EF launch condition is to provide:
1. Consistency of field measurements when different sources are
used; reducing loss measurement uncertainty from greater than 40 %
to less than 10 % on a dB basis.
2. A provisional worst-case launch condition for IEEE 802.3
(Ethernet) and INCITS T11 (Fibre Channel) compliant transceivers
used in high-speed networks (≥1Gbps).
3. A template for compliance at the output of launch cords.
4. Comparable insertion loss of a single connection and/or
splice at both 850 nm and 1300 nm.
5. Increased harmonization of a metric that defines multimode
launch conditions for testing.
Although the focus of this document is to assist field personnel
in understanding alternative EF launch condition implementation
options, the concepts in this TSB may be applicable to certain lab
testing situations where EF launch condition compliance is
required.
Note: The source launch conditions are specified for the launch
cord output. It is presumed that equipment, as supplied, has been
verified by the manufacturer to produce the specified launch
measured per TIA-455-203-A (FOTP-203-A) or IEC 61280-1-4 Ed.
2.0..