More info
Full Description
This standard establishes minimum requirements for double-disc swingcheck valves, 2-in. (50-mm) through 48-in. (1,200-mm) NPS, with various body and end types for raw, potable, and reclaimed water having a pH range from 6 to 12 and a temperature range of 33125F (0.652C).
1.1.1 Body types. Valves described in this standard are provided with wafer or threaded-lug ends for installation between ANSI Class 125 flanges or grooved ends for use with IPS pressure pipe.1.1.2 Gray-iron pressure ratings. The minimum design working water pressure for gray-iron valves shall be 200 psig (1,380 kPa) for 2-in. through 12-in. (50-mm through 300-mm) NPS inclusive and 150 psig (1,030 kPa) for 14-in. through 48-in. (350-mm through 1,200-mm) NPS inclusive. 1.1.3 Ductile-iron pressure ratings. The minimum design working water pressure for ductile-iron valves shall be 250 psig (1,720 kPa) for 2-in. through 48-in. (50-mm through 1,200-mm) NPS inclusive. 1.1.4 Fluid velocity rating. The maximum fluid velocity shall be 16 ft/s (4.9 m/s). 1.1.5 Installations. Double-disc swing-check valves are designed for installation in horizontal pipelines and in vertical lines with flow in the upward direction. Valves must be installed with hinge pins in the vertical position for horizontal pipeline installations. 1.1.6 Excepted conditions. Conditions of water hammer, hydraulic pulsation, and excessive noise are beyond the scopeThis standard can be referenced in purchase documents for double-disc swingcheck valves, which are described by the scope as defined previously.